FireAlarmGuy
Technical bulletin

Silent Knight SWIFT pull stations — legacy low-battery bulletin still worth knowing

Honeywell still features a technical bulletin for certain WSK-PULL-DA wireless pull stations that can generate a premature and erroneous low-battery warning. The bulletin is dated July 20, 2022 — this is not a new 2026 recall.

By Eric Aubrey · CT E-1 · NICET Fire Alarm Systems Level III

What the bulletin says

Honeywell Technical Bulletin TB22.1SK identifies the WSK-PULL-DA Silent Knight SWIFT pull station as having the potential to generate a premature, erroneous low-battery notification within a few months of installation.

Honeywell says the notification itself is not a safety issue, but also says low-battery warnings should be addressed promptly because system-operation problems could eventually arise if a legitimate battery condition is ignored.

Which units are potentially affected?

The bulletin identifies products with date codes 8xxx, 9xxx, 0xxx, 1xxx, 201x, 202x, and 203x, where “x” can be any number. The bulletin includes a product-label illustration showing where the four-digit date code is located.

Does every affected pull station need replacement?

No. Honeywell's bulletin says SWIFT pull stations that are operating without the low-battery issue do not need to be replaced. Units in the identified date-code range that exhibit a premature low-battery warning are directed through the normal warranty-return process.

What a service technician should do

Why keep an older bulletin on FireAlarmGuy?

Installed fire alarm equipment can remain in service for decades. A 2022 bulletin can still save troubleshooting time in 2026 when a technician encounters the affected device in the field. It belongs in the reference library — just not presented as brand-new news.

Official sources

Honeywell resource page and bulletin checked September 25, 2026. The underlying technical bulletin is dated July 20, 2022.